Wacker Neuson EHB 10 series Návod k obsluze Strana 51

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 60
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 50
EHB 11 Technical data
51
12.4 Extension cable
Only use permitted extension cables, see chapter Safety.
Refer to the following table for the required cross-section area of the exten-
sion cable:
Note: Refer to the nameplate or the chapter Technical data (via the item
number) for the type designation and voltage rating of your machine.
WARNING
Electrical voltage.
Injuries from electrocution.
f Check power cable and extension cable for signs of damage.
f Only use extension cables for which grounded conductors are connected to
the plug and the coupling (only for machines of class rating I, see chapter
Technical Data).
Voltage
[V]
Extension
[m]
Cross-section
area of cable
[mm
2
]
110–127 1~ < 8 1.5
< 13 2.5
< 20 4.0
< 30 6.0
220–240 1~ < 27 1.5
< 44 2.5
< 70 4.0
< 105 6.0
Zobrazit stránku 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 59 60

Komentáře k této Příručce

Žádné komentáře