G 3.3A Operation
wc_tx000150gb.fm 19
4.6 Use of Extension Cords
When a long extension cord is used to connect an appliance or tool to
the generator, a voltage loss occurs—the longer the cord, the greater
the voltage loss. This results in less voltage being supplied to the
appliance or tool and increases the amount of current draw or reduces
performance. A cord with a larger cross section will reduce the voltage
loss.
CAUTION: Operating equipment at low voltage can cause it to
overheat.
Use the table as a guide for selecting proper cable size.
Use only tough rubber-sheathed cable in accordance with IEC 245-4.
Damaged cords can cause electrical shock. Electric shock can cause
serious injury or death. DO NOT use worn, bare, or frayed cords.
Replace damaged cords immediately.
Minimum Extension Cord Size 230V
Volts Total length of cord in meters
230 V 0 - 30 30 - 60
Amp Rating
Cross sectional area of wire in mm
2
2 0.75 1.5
41.5 2.5
61.5 4
82.5 4
10 2.5 6
15 4 10
20 6 10
25 6 16
30 10 16
WARNING